GI Volume Control Dampe

Product Description

The GI Volume Control Damper (VCD) is designed to regulate and balance airflow in HVAC duct systems. It is installed in supply, return, fresh air, and exhaust air ducts to provide precise airflow adjustment during system balancing and commissioning. Dampers are available with manual quadrant operation or motorized actuators and can be supplied with parallel or opposed blade configurations.

Technical Specifications

Parameter Specification
Product Type GI Volume Control Damper
Application Air volume balancing and airflow regulation
Frame Material Galvanized Iron (GI) Sheet
Frame Thickness 1 mm & 1.2 mm (Standard); 1.5 mm Optional
Blade Thickness 1 mm & 1.2 mm (Standard); 1.5 mm Optional
Blade Material Galvanized Steel V Blade (Standard)
Blade Operation Opposed Blade (Standard); Parallel Blade (Optional)
Frame Depth 150 mm as Standard
Flange Width 25 mm Sheet Flange, 35 mm TDF Flange
Operation Manual / Motorized
Bearings Self-lubricating Nylon Bushes / Brass Bushes
Linkage Mechanical Linkage
Handle GI Locking Quadrant with Position Indicator
Leakage Option Foam/Silicone Blade Gasket
Finish Pre-Galvanized Finish (Optional Powder Coating)
Mounting Horizontal or Vertical