Brand

Navajyothi Air Flow

Product

NJ-Door Grille

Application

Exuast / Return air distribution for HVAC ventilation and air-conditioning systems

Product Description

Navajyothi Air Flow Door Grills also known as Aluminium Non Vision Door Transfer Grille is designed to provide efficient air transfer through doors or partition walls while preventing direct visibility between adjacent spaces. The grille features inverted V-shaped blades that ensure privacy without significantly restricting airflow. It is commonly used in HVAC ventilation systems for commercial, institutional, healthcare, and residential buildings.

Technical Specifications

Parameter Specification
Material High-quality Extruded Aluminium profile
Blade Type Fixed Inverted “V” (Chevron) Non Vision Blades
Frame thickness 1.2 mm thickness
Flange 30 mm as standard
Blade thickness 1.2 thickness
Blade Spacing 18–20 mm (Typical)
Frame Type Single Frame / Double Frame
Door Thickness 25–50 mm (Standard), custom available
Standard Finish Natural Anodized / Powder Coated
Standard Colours RAL 9010 White, RAL 9016 White
Optional Colours Any RAL Colour shades
Installation Screw Fixing (Visible or Concealed)
Corrosion Resistance Excellent
Construction Features
  • Heavy-duty extruded aluminium frame.
  • Fixed non-vision chevron blades eliminate direct line of sight.
  • Double telescopic frame provides neat appearance on both sides of the door.
  • Corrosion-resistant aluminium construction.

Standard Sizes :

Width (mm) Height (mm)
150 150
200 100
200 200
300 150
300 200
400 200
400 300
450 300
600 150
600 200
600 300
Custom Sizes Available
Applications
  • Office Doors , Toilet Doors, Hospitals , Hotels, Schools
  • Clean Rooms , Electrical Rooms, Utility Rooms, Commercial Buildings
Optional Accessories
  • Insect Screen
  • Opposite/Counter Frame
  • Black Finish for Dark Room Applications
  • Custom Powder Coating

Double Frame Door Grille

Single Frame Door Grille

Performance Data Table :

Grille Size
Width x Height
(mm)
Gross
Area
(m²)
Effective Free
Area Ak (m²)
Air Volume
Flow Rate (l/s)
Air Volume
Flow Rate (m³/h)
Core
Velocity
(m/s)
Static Pressure
Drop ΔP (Pa)
Noise Criterion
(NC Level)
300 x 150 0.045 0.019 10 36 0.5 2 <15
20 72 1.1 7 <15
30 108 1.6 15 18
40 144 2.1 27 25
300 x 300 0.090 0.041 20 72 0.5 2 <15
40 144 1.0 6 <15
60 216 1.5 14 17
80 288 2.0 24 24
450 x 300 0.135 0.062 30 108 0.5 2 <15
60 216 1.0 6 <15
90 324 1.5 13 17
120 432 1.9 23 23
600 x 300 0.180 0.083 40 144 0.5 2 <15
60 216 1.0 6 <15
120 432 1.4 13 16
160 576 1.9 22 22
600 x 450 0.270 0.124 60 216 0.5 2 <15
120 432 1.0 6 <15
180 648 1.5 13 16
240 864 1.9 22 22
600 x 600 0.360 0.165 85 306 0.5 2 <15
165 524 1.0 6 <15
250 900 1.5 14 17
330 1188 2.0 24 23

Our Drawing

Reference drawing